UPS Modules - Listed below are 208 input units without internal isolation transformers. Systems with internal isolation transformers are also available. Wilson Engineered Systems general recommendation is to provide isolation either before or after the UPS module to allow a true external catastrophic bypass panel around the UPS. We can provide these transformers as part of the overall system.

Complete UPS System requires UPS module, batteries (internal or external), startup. Optional items are additional or external batteries, maintenance bypass panel, network monitor, remote mimic panel, facility monitor, battery monitoring.

UPS Modules

WES Part #s (UPS/Startup) kVA/kW # of inputs Input Voltage Output Voltage Battery Time
103422 / 102880 15 / 12 1 120/208 120/208 internal 10 minutes
103423 / 102880 15 / 12 2 208 main, 120/208 bypass 120/208 internal 10 minutes
/ 102880 15 / 12 1 120/208 120/208 external
103424 / 102880 15 / 12 2 208 main, 120/208 bypass 120/208 external
103448 / 103449 25 / 20 1 120/208 120/208 internal 5 minutes
103428 / 103449 25 / 20 2 208 main, 120/208 bypass 120/208 internal 5 minutes
/ 103449 25 / 20 1 120/208 120/208 external
103429 / 103449 25 / 20 2 208 main, 120/208 bypass 120/208 external
102881 / 102882 30 / 24 1 120/208 120/208 internal 5 minutes
103868 / 102882 30 / 24 2 208 main, 120/208 bypass 120/208 internal 5 minutes
103904 / 102882 30 / 24 1 120/208 120/208 external
103914 / 102882 30 / 24 2 208 main, 120/208 bypass 120/208 external
102883 / 102884 50 / 40 1 120/208 120/208 internal 5 minutes
103693 / 102884 50 / 40 2 208 main, 120/208 bypass 120/208 internal 5 minutes
103450 / 102884 50 / 40 1 120/208 120/208 external
103503 / 102884 50 / 40 2 208 main, 120/208 bypass 120/208 external
102885 / 102886 80 / 64 1 or 2, field selected 208 main, 120/208 bypass 120/208 external
           
           


External Battery Cabinet 

For longer time needs external battery cabinets are available. The Series 4200 UPS requires a nominal 288 VDC battery. These batteries will float charge at 324 to 331 VDC. During a discharge the battery energy will be used as the battery drops to approximately 240 VDC. The battery cabinet will have a DC breaker with monitoring contacts and the ability to remote trip in either a safety emergency or when the batteries become too depleted and further discharge would be harmful. There are a multitude of battery configurations available. Below are selections for nominal time and for selections which make sense in terms of good price points and serviceability. Generally we recommend against batteries in the 100 lb each range for service and changeout reasons. Batteries are C&D High Rate Sealed Valve regulated Batteries

WES Part# Associated UPS Runtime @ Load DC Breaker Size (amps) Dimensions Weight (pounds)
104038 15 kVA 29 minutes @ 12 kW 60 29"w x 31.6"d x 59.8"h 1,018
104039 15 kVA 94 minutes @ 12 kW 60 29"w x 31.6"d x 59.8"h 2,156
104040 25 kVA 14 minutes @ 20 kW 100 29"w x 31.6"d x 59.8"h 1,018
104041 25 kVA 52 minutes @ 20 kW 100 29"w x 31.6"d x 59.8"h 1,988
104042 30 kVA 18 minutes @ 24 kW 125 29"w x 31.6"d x 59.8"h 1,340
104043 30 kVA 41 minutes @ 24 kW 125 29"w x 31.6"d x 59.8"h 2,156
103924 50 kVA 15 minutes @ 40 kW 225 29"w x 31.6"d x 59.8"h 1,748
104044 50 kVA 22 minutes @ 40 kW 225 29"w x 31.6"d x 59.8"h 2,156
103734 80 kVA 11 minutes @ 64 kW 300 29"w x 31.6"d x 59.8"h 2,156
Qty 2 of 103734 80 kVA 29 minutes @ 64 kW 300 2 @ 29"w x 31.6"d x 59.8"h 2 @ 2,156

Maintenance Bypass Panels

All electrical equipment shuild have maintenance performed at least annually. Certainly a critical power system such as a UPS should be maintained. To properly do so either a maintenance bypass panel, second isolated UPS or load shutdown is required. We recommend a maintenance bypass panel on all three phase UPS. An internal maintenance bypass within the UPS cabinet does not meet this need. For safe servicing the bypass panel must be external. That is also why voltage stepdown should not occur within the UPS. Below are the part numbers and sizes for the proper external maintenance bypass.

WES Part# Associated UPS Bypass Breaker Size (amps) Dimensions Weight (pounds)
104045 15 kVA 80 30"w x 10"d x 43"h 190
104046 25 kVA 100 30"w x 10"d x 43"h 190
103432 30 kVA 125 30"w x 10"d x 43"h 190
103433 50 kVA 225 30"w x 10"d x 43"h 190
103394 80 kVA 300 36"w x 12"d x 61"h 325

Monitoring Accesories

A network UPS monitor will allow direct communication from the UPS to an ethernet network. This allows remote viewing of UPS status as well as network based logging of UPS performance. During non standard conditions SNMP traps or emails may be sent out. Other monitoring options include a network based facility monitor interfacing with the UPS alarm contacts such as "On Inverter", "On Bypass", "On Battery", "Low Battery" or "Unit Fault". Typically with this monitor additional conditions such as UPS room or area temperature will also be monitored. The lowest level of remote monitoring would be a remote status alarm panel which provides LEDs and a system mimic schematic to indicate UPS status or alarm conditions. The remote status alarm panel includes an audible alarm.

WES Part# Description
103736 Toshiba Remote Eye II network interface module with self hosted web page, SNMP and email capability
  Facility Monitor interfacing with UPS dry contacts and providing UPS room/area and battery cabinet temperature
103975 Wall Mounted Remote Status Alarm Panel with LEDs, mimic diagram and audible alarm
 


   

Site Update 03/26/08
  904-880-0118 * www.wilsonengineeered.com